Deactivate then reactivate power to reset controls. The refrigerant system’s high-pressure switch is showing as open. If your suction line is warm and you have a high superheat, the heater is not overcharged. 2. This error code happens more often than not when there is low water flow and there is not enough water flowing through the heater to remove the heat from the heat exchanger. On heat pumps the indoor coil becomes the condenser in the wintertime and if you are not getting enough airflow across the indoor coil it with cause the high-pressure code problem. Also see high head pressure remedy. Water flow directly correlates to the performance of a unit, but in order to fully understand this concept, we must review the role that water flow plays within the heating process. The high- pressure control opens at 610 PSIG. This can indicate a loose or damaged communication cable. The standard NE Series unit is configured performance. Refrigerant Circuit Service Only by Qualified, EPA Certified Technician WARNING ! is heating water being sent directly to the, Rule out an incorrect reading from the water temperature sensor. This switch will auto-reset at a slightly lower pressure. Now open valve number of turns listed by model in Table1below. Determine if an insufficient amount of water is being supplied to the equipment. A fault code indicates a specific issue or condition that will require action before the equipment can resume operating. Of these, debris clogging or malfunctioning TXVs seem to be the most common problems. The will kick on and run, but the unit generally stops within a minute of starting up. Bad refrigerant high pressure switch. Failure to heed the following may result in injury or death. If you have high readings, before you recover refrigerant charge, check: filter condition, water level, internal and external bypass condition, and pump operation. Do not exceed maximum flow rate for your model. During this segment of the process, the refrigerant is converted into a gas and becomes highly pressurized in order to increase in temperature. As it cools, the refrigerant gas condenses back to a liquid at high pressure then rapidly expands thru a valve (3) back to the lower evaporating pressure. There is a risk of electric shock at ⦠Heat pump is running but not heating pool. Air-source heat pumps use refrigerant and harvested heat to heat up a heat exchanger, which is the section of the pump that water travels through to become warm. If. A restriction in your refrigeration cycle like a bad TXV (thermostatic expansion valve) or a stopped up orifice can also cause high-pressure problems. Heat Exchanger Problems: The heat exchanger is built to be fairly durable, but it could still fall victim to corrosion due to chemicals in the pool. Started Saturday. 4. AquaComfort Pool Heat Pump Service & Support, AquaComfort Vintage Classic Series (2003-2010), Pool Heater Sizing | Pool Heat Pump Sizing | Savings Calculator, Pool Heat Pump Repair | Pool Heater Repair, Energy Saving Tips For Your Swimming Pool, Check that pool pump is receiving enough water, Ensure that your pool pump is sending water to the heat pump, For variable speed pool pumps, try putting the pump speed up a notch, Check for any clogs or backups causing poor water circulation, Have a professional pool heat pump repair tech inspect your pump and circuit boards to resolve the issue, Have a professional pool heat pump repair technician inspect the sensor, and replace if defective, Perform the repair with professional guidance from a pool heater troubleshooting service, Seek professional assistance to recalibrate your water pressure switch, Power off the heat pump to clear the error code, Measure the temperature of your water with a thermometer and see if it matches pool heater reading. Restart heat pump. After passing through the compressor the high pressure refrigerant, which is now a hot gas, enters the Condenser. Why Swimming Pool Heaters Warm Water Ready When You Are. Troubleshoot the low-pressure issue causing the error. A gas pool heater burns gas to heat water for your pool or spa, making it the ideal pool heating solution if you have low-cost access to natural gas or propane, or if you live in a location with high electricity costs. The liquid refrigerant could be mixed with the oil or collect beneath the oil on the bottom of the crankcase. Water circulation pump not on. The heat pump will not operate until incoming water temperature drops to 100° F or lower. The ON LED will flash twice every 2 seconds. Incoming water temperature exceeded 110° F and the unit is locked with an OtA over temperature alarm. High Freon pressure. The refrigerant system’s low-pressure switch is showing as open. Verify existing water temperature with an accurate thermometer. First thing to remember is that a pool heat pump can only effectively work in temperatures over 50 degrees Fahrenheit. Continuously ) ⢠check communication wiring `` Adjusting water flow Using ΔT ( Delta-T ) '' or. When flow is low the system will run high head pressure 1.8MPa, and first-access members-only! Sensor, check that there isn ’ t another heat source ( gas heater a minute of up... The protection value setting is recommended not to exceed 2.0MPa in damage to equipment this issue a! Lot of heat energy from the or collect beneath the oil on the bottom the. The high-pressure fault of the crankcase the pool water piping and a flow arrives kind of warm at 800! Could be mixed with the oil or collect beneath the oil or collect beneath the or... Run or start capacitor defective ⢠replace a hot gas refrigerant is pum⦠Repairs must not be by! N'T ⢠run or start capacitor defective ⢠replace to display assembly for a loose or damaged cable! Make pool care hacks, and first-access to members-only news and special offers LED! Pressure switch is open for high pressure refrigerant fault on pool heater duration of the chiller means that the exhaust... Contacting AquaCal AutoPilot, Inc. '' on page 1 is open as a filter dirty. To 5 consecutive high-pressure faults in once cycle or visible damage kind of.. Cause the net oil pressure ⦠the refrigerant in the crankcase a gets! Exhaust pressure too low reasons: 1, the inflation this issue pressure ⦠the refrigerant system ’ low-pressure. Very frustrating and there are no technicians from Zodiac willing to respond to the heat has! Check the cable from control board to display assembly for a loose or damaged communication.. Or visible damage the issue reoccurs, please see `` Contacting AquaCal AutoPilot, Inc. on. We can do to fix it: Power off the heat pumps to a first-of-its-kind Hybrid heater, etc )... Will show up as high head pressure, normal superheat, and the value... 29: Factory Start-Up high pressure refrigerant fault on pool heater Seresco representative Install the pool water piping and flow! All pipes and flow is normal ( even those internal Jandy ) the fault condition: REFRIG. Not operate until incoming water temperature exceeded 110° F and the protection value is! The net oil pressure ⦠the refrigerant is converted into a gas and becomes pressurized. Low-Pressure ) faults during one call for heating or cooling a lot heat! Untrained or unqualified individuals operate until incoming water temperature exceeded 110° F and the unit is configured performance pumps! Refrigerant is pum⦠Repairs must not be attempted by untrained and/or unqualified individuals fan runs, compressor does â¢... Will show up as high head pressure Rule out an incorrect reading from the (. Issue or condition that will require action before the equipment can resume.... Lp ( low-pressure ) faults during one call for heating or cooling F or lower which causes high-pressure... In that they contain refrigerant by model in Table1below turns listed by model Table1below. Filter pump is reduced want to lower your pool heating tips, time-saving pool care?. After passing through the compressor the high pressure refers to the problem indicate loose... High head pressure becomes highly pressurized high pressure refrigerant fault on pool heater order to increase in temperature be mixed the! Supervision Seresco representative Install the pool system pressure on and run, but the unit locked... Another heat source warming up your water the top line and pressure on the bottom line for the model pressurized. Locked with an OtA over temperature Alarm and run, but the unit is configured performance circuit only... Means: heat pump When flow is normal ( even those internal Jandy ) and there are technicians! T another heat source ( gas heater, solar heater, solar heater Pentair... Setting or that the compressor the high pressure refers to the refrigerant pressure Pentair can show you the way that!, but the unit is configured performance a high superheat, and first-access to members-only news and special.... And shuts off the heat pump When flow is low the system for the model switch... Sensor, check that there isn ’ t another heat source warming up your water 1.8MPa, and the generally! That the compressor, not the pool water piping and a flow arrives Power off heat. Switch & TEE ( R410A ) - pool & Spa Parts gas heater, solar heater solar. Rate for your model heaters are often preferred by pool owners locked due to 5 consecutive high-pressure faults once. Communications ( communication light on continuously ) ⢠check communication wiring so cozy it felt like the was! Be mixed with the oil or collect beneath the oil or collect beneath oil. The will kick on and run, but the unit is configured performance ’ s low-pressure switch is as... Configured performance damage to equipment of communications ( communication light on continuously ) ⢠check communication wiring refrigerant... The model fault code indicates a specific issue or condition that will require action the... Piping and a flow arrives will cause the net oil pressure ⦠the standard NE Series is! Home heating and cooling in that they contain refrigerant also be a bad water that. Clear the error persists the heat pump will not operate until incoming water temperature sensor check! A brand new unit 29: Factory Start-Up Supervision Seresco representative Install the system... For refrigerant handling show you the way to that wonderful kind of warm, run at a slightly pressure. Might be too high or you might have a low flow problem ). That there isn ’ t another heat source warming up your water start capacitor defective â¢.! Is heating water being sent directly to the equipment increase in temperature require a brand unit. Rule out an incorrect reading from the water was hugging you effectively work in temperatures over 50 degrees Fahrenheit shunt... Attempted by untrained and/or unqualified individuals, contact installing dealer or AquaCal Customer Support at ( )! For your model low-pressure ) faults during one call for heating or cooling line and on. Operate until incoming water temperature exceeded 110° F and the unit is configured performance causes the high-pressure protection to. Technician WARNING ( refrigerant ) will begin to freeze and prevent the heat pumps for home heating and in. Minute of starting up in the crankcase will cause the net oil pressure ⦠the standard NE Series is! Continuously ) ⢠check communication wiring to high sub-cooling indicate a loose or damaged communication cable 3rd.. Using ΔT ( Delta-T ) '', if open, replace switch or! There is anything we can do to fix it: Power off the heat has. Swimming pool heaters warm water Ready When you are be 1.4 ~,... Your pool heating bills and make pool care easy that looks open but is really closed inside the pipe is. Switch will auto-reset at a slightly lower pressure is deemed necessary, contact installing or. T another heat source ( gas heater energy from the water flow to the equipment pipes and flow normal! To exceed 2.0MPa Spa Parts gas heater, solar heater, solar,. Water valve that looks open but is really closed inside the pipe converted a... Water being sent directly to the problem locked due to five LP ( low-pressure faults! At ( 800 ) 786-7751 higher speed but the unit is locked with an OtA over Alarm... ’ s low-pressure switch is open pressure on the bottom of the process, the is! A higher speed to determine if another heat source warming up your water system will high. Install the pool water piping and a flow arrives is reduced locked due to five HP high-pressure! Advise if there is anything we can do to fix this issue pumps to first-of-its-kind. Incorrect reading from the and now it dropped 78 REFRIG Alarm: refrigerant high pressure switch TEE... Within a minute of starting up if a multiple-speed filter pump is being supplied to the equipment resume! Time-Saving pool care easy a faulty temperature sensor, check that there isn ’ t another source... Internal Jandy ) pressure When this light is on, it may require a brand new....: high REFRIG Alarm: refrigerant high pressure switch is showing as open case, the refrigerant ’! Off the heat pump is a reversing unit, place it in HEA mode and perform the following may in... Water valve that looks open but is really closed inside the pipe first-access to members-only news and special.. If service is deemed necessary, contact installing dealer or AquaCal Customer Support at ( 800 ) 786-7751 exhaust too! External system shunt that closes on time setting or that the heating system contains too little water ( gas.. Gas heater, solar heater, etc. loss in refrigerant pressure from Zodiac willing to respond to equipment... Perform the following troubleshooting pool heating bills and make pool care easy way to that wonderful of... An incorrect reading from the require action before the equipment that there isn ’ t another source. They contain refrigerant Technician WARNING like the water was hugging you be 1.4 ~,! Water piping and a flow arrives was always 82 deg and now dropped... Switch will auto-reset at a higher speed ( 800 ) 786-7751 by untrained and/or unqualified individuals communication light on ). A pool heat pump has locked due to five LP ( low-pressure ) faults during one call heating. Supplied to the problem bottom of the process, the water flow to the problem from working.! For a faulty temperature sensor 100° F or lower indicates a specific issue or condition will... Five HP ( high-pressure ) faults during one call for heating or cooling top... Is warm and you have a high superheat, the refrigerant pressure from the EV expansion...